EVIPOWER Premium Monoblock R32

The new C&H EVIPOWER INVERTER PREMIUM heat pumps provide maximum comfort in the home thanks to the latest EVI technology, which extends the operating range of the unit and allows the heat pump to produce 50°C outlet water at -25°C outdoor temperature, and they are also very quiet and save the environment, because they use environmentally friendly R32 gas as a refrigerant. Available in a power range of 8 kW for 1-phase units and from 12.5 to 23 kW for 3-phase units.


DESCRIPTION:

  • Exclusive design of premium ABS plastic body
  • Very quiet operation for 23 kW – only 46 dB(A)
  • 5″ color touch control panel
  • Configurable via BMS (RS485) and remote control
  • Patented shell and tube heat exchanger
  • GRUNDFOS circulation pump
  • Panasonic EVI inverter compressor
  • Quick start system at low temperatures
  • Cascade mode possible

SPECIFICATIONS

Model   CH-HP08UIMPRK-P CH-HP12UIMPRM-P CH-HP23UIMPRM-P
HEATING MODE (T OFF (DB / WB): 7/6 ° C, T WATER 30/35 ° C)        
Heating capacity* kW 2.30 ~ 8.20 3,80 ~ 12,50 7.00 ~ 23.00
Electricity consumption in heating mode kW 0,50 ~ 1,84 0,8 ~ 2,95 1,27 ~ 5,20
HOT WATER HEATING MODE – EXTERNAL T (DB / WB): 20/15 °C, T WATER 15/55 °C        
Heating capacity kW 3.00 ~ 9.50 4.15 ~ 16.00 10.20 ~ 23.00
Electricity consumption in hot water heating mode kW 0,62 ~ 2,30 0,90 ~ 3,85 2,10 ~ 6,29
COOLING MODE (T EXTERNAL (DB / WB): 35/24 °C, T WATER 12/7 °C)        
Cooling capacity kW 1,56 ~ 6,00 2:20 ~ 10:00 6,30 ~ 18,4
Electricity consumption in cooling mode kW 0,63 ~ 2,36 1,10 ~ 3,80 1,63 ~ 7,05
Energy efficiency class (35°C)   A +++ A +++ A +++
Energy efficiency class (55°C)   A++ A++ A++
PURPOSE (35°С)   4,8 4,77 4,71
PURPOSE (55°С)   3,35 3,44 3,46
Refrigerant   R32 R32 R32
Amount of refrigerant kg 1,3 1,8 2,3
Electrical connection   230V ~ / 50Hz 380V / 3 ~ / 50Hz 380V / 3 ~ / 50Hz
Integrated electric heater /
Compressor   Panasonic EVI Panasonic EVI Panasonic EVI
Circulation pump   Grundfos Grundfos Grundfos
Circulation pump head m 5 4,5 6,9
Water connection toll 1″ 1″ 1″
Water flow rate m³ / h 1 1,7 2,9
Helirõhutase (1 m) dB (A) 42 45 46
Sound power (according to standard EN12102) dB (A) 57 60 61
Net dimensions (LxWxH) mm 1167x420x790 1287x500x928 1247x540x1329
Neto kaal kg 80 100 160
Temperature operating range °C  -25-43  -25-43  -25-43
Max. inflow temperature °C 60 60 60
Max. inflow temperature (at -25 °C) °C 55 55 55

* Heating mode – ambient temperature (DB / WB): 7/6°C, Temp. water (inlet/outlet): 30/35°C
** Hot water heating mode – ambient temperature (DB / WB): 20/15°C, water tank temperature from 15℃ to 55℃
*** Cooling mode – ambient temperature (DB/WB): 35/24°C, Temp. water (in/out): 12/7°С

Cooper & Hunter Support

-

Support 24H

    Please fill out all required fields