Heat pump EVIPOWER industrial series

Industrial heat pump EVIPOWER ON-OFF


DESCRIPTION:

  • Five operating modes: Heating, Cooling, DHW, Heating + DHW, Cooling + DHW
  • Scroll compressors with EVI technology
  • Smart defrost
  • Managing multiple modules
  • Automatic reset on partial failure
  • Wide temperature range of effective work: from -30 ° С for heating and up to + 45 ° С for cooling.
  • Quiet Mode
  • Remote control
  • Compressor overload protection
  • High / low leaving water temperature protection


Remote control option:

Additional equipment:

Additional controller Smart Pro 360

MODELS:

TECHNICAL SPECIFICATIONS:

Model     CH-HP16UMNM CH-HP42UMNM CH-HP84UMNM
HEATING MODE (T OFF (DB / WB): 2/1 ° C, T WATER 30/35 ° C)          
Heating capacity   kW 15,7 42 84
Energy consumption in heating mode   kW 3,47 10 20
Nominal current   A 6 17,8 42,4
COP     4,52 4,2 4,2
COOLING MODE (T EXTERNAL (DB / WB): 35/24 °C, T WATER 12/7 °C)          
Cooling capacity   kW 11,5 27,3 59,0
Energy consumption in cooling mode   kW 4,0 10,6 21,9
EER     2,88 2,58 2,69
HOT WATER HEATING MODE – EXTERNAL T (DB / WB): 20/15 °C, T WATER 15/55 °C          
Heating capacity     19,00 50,00 100,00
Energy consumption in hot water heating mode     4,1 10,8 22,0
COP     4,63 4,63 4,55
Electrical connection     ~380V/3f/50Hz ~380V/3f/50Hz ~380V/3f/50Hz
Refrigerant     R410 R410 R410
Water flow rate   m³ / h 2,6 8,5 17
Water connection   inches 1 1”1/2 DN80
Pressure loss in the heat exchanger   kPa 60 60 65
Sound pressure level   dB(A) 60 68 73
Net Dimensions (WxDxH)   mm. 980x390x1280 1413x854x2000 2180x1080x2100
Gross Dimensions (WxDxH)   mm. 1050x430x1400 1490x900x2160 2260x1130x2260
Weight Net kg. 143 475 778
  Ugly kg. 159 500 843
Operating temperature range   °C -30°C ~ 43°C -30°C ~ 43°C -30°C ~ 43°C
Max. inflow temperature   °C 60 60 60

Industrial heat pump EVIPOWER INVERTER

DESCRIPTION:

  • Cooling operating temperatures -15°C … +52°C
  • Heating operating temperatures -20°C … +40°C
  • High efficiency and energy saving with all DC inverter compressor and fan
  • Ülivaikne ja lai tööulatus
  • Easy installation, excellent compatibility, up to 16 individual devices can be modulated, intelligent control
  • Long-distance one-key ON/OFF control
  • With a water pump switch function to extend the life of the water pump
  • Convenience and energy saving
  • Powerful self defense
  • High reliability
  • Balance of operation of each compressor
Model     CH-HP35UIMRM CH-HP65UIMRM CH-HP137UIMRM
Cooling capacity   kW 32 60 130
Heating capacity   kW 35 65 137
Energy consumption in cooling mode   kW 11,7 20,8 43,9
Energy consumption in heating mode   kW 10,6 19,9 41

TECHNICAL SPECIFICATIONS:

Model CH-HP35UIMRM CH-HP65UIMRM CH-HP137UIMRM
Noise level dB(A) 62 68 69
Power supply 380-415V AC 3Ph 50Hz
Compressor type closed rotor
Number of compressors 1 2 4
Water flow rate m³/h 5,5 10,32 22,36
Water resistance kPa 80 55 60
Max pressure MPa 4,6
Connection method Flanges
Connection thread G1 1/4 male thread G2 external thread DN80
Air fan W 750×2 750×2 750×4
Airflow volume m³/h 2×0.63×104 2×1.2×104 4×1.55×104
Width mm 1340 2200 2305
Depth mm 845 965 1980
Height mm 1605 1675 2120
Nуе weight kg 405 686 1286
Working weight kg 445 755 1413

Electrical connections (min. cross-sectional area of ​​power cable, mm²):

Model Power source
Live line Neutral line Ground line Air switch (A)
CH-HP35UIMRM 380V-415VAC 3Ph 50Hz 6 6 6 32
CH-HP65UIMRM 380V-415VAC 3Ph 50Hz 16 16 16 63
CH-HP137UIMRM 380V-415VAC 3Ph 50Hz 35 16 16 150