Duct units


DESCRIPTION:

  • Easy installation;
  • Low noise and compact size;
  • The widest range of products supplied to the warehouse: from 350 m 3 / hour to 12,000 m 3 / hour;
  • For units with flow rates from 350m 3 / hour & nbsp; up to 1000m 3 / hour & nbsp; including three fan speeds;
  • For installations with flow rates from 350m 3 / hour & nbsp; up to 1000m 3 / hour inclusive, they do not require condensate drainage, since the recuperator is made of paper.

MODELS:

Model : HRV 3.5 5 8 10 15 20 30
Power grid parameters ~ 22-240V/
50Hz/1ph
~ 22-240V/
50Hz/1ph
~ 22-240V/
50Hz/1ph
~ 22-240V/
50Hz/1ph
~ 380-415V/
50Hz/3ph
~ 380-415V/
50Hz/3ph
~ 380-415V/
50Hz/3ph
Air consumption H 350 500 800 1000 1500 2000 3000
(m3/hour) M 260 380 600 750 1500 2000 3000
L 210 300 480 600 1500 2000 3000
External static pressure (Pa) H 100 100 110 110 150 150 220
M 80 80 85 85 150 150 220
L 60 60 65 65 150 150 220
External pressure, % H 71 68 70 75 73 71 70
M 73 70 72 77 73 71 70
L 75 72 74 79 73 71 70
Efficiency of enthalpy exchange, % Heating H 65 62 63 66 65 62 62
M 67 64 65 68 65 62 62
L 68 65 67 70 65 62 62
Cooling H 61 57 60 62 60 58 58
M 63 59 62 64 60 58 58
L 65 61 64 65 60 58 58
Power supply cable Amount 3 3 3 3 5 5 5
Space mm² 1 1 1 1 1.5 1.5 1.5
Power consumption W 165 262 400 440 600 950 2800
The sound power of the built-in device dB (A) 37 39 45 46 48 50 54
Dimensions (mm) height 306 306 380 380 452 452 572
width 800 800 832 832 1210 1210 1340
depth 879 879 1016 1016 1215 1215 1550
Weight Kg 45 45 70 70 100 100 211

Cooper & Hunter Support

-

Support 24H

    Please fill out all required fields